1. Entering the clean area:

1.1 When the person entering the clean area opens the outer door, the electric lock of the inner door is automatically locked to prevent the unpurified air in the air shower from flowing into the clean area, the light in the air shower is lit, and the working indicator light outside the door is on.

1.2 After entering the air shower and closing the outer door, the voice prompts: "Hello, please stand in the sensing area". The infrared sensor of the system starts to detect whether there is someone, and if someone is detected, the system will transfer to the air shower process.

1.3 Before the air shower, the inner and outer doors are locked, the fan starts to start the air shower, and at the same time, the countdown of the air shower starts. Voice prompt: "Working, please turn your body 360 degrees".

1.4 If the system does not detect anyone in the air shower room within the specified time after the outer door is closed, the inner and outer doors of the system will automatically unlock and return to the standby state, and the infrared will continue to detect. If someone is detected, the inner and outer doors will be locked, and the air shower room will start to air shower .

1.5 During the air shower process, when someone presses the up, down, and lighting switches, the voice will prompt: "It is working, please do not touch the switch casually".

1.6 During the air shower process, when someone presses the emergency stop switch, the air shower will end. Press the emergency stop button again to cancel the emergency stop state.

1.7 After the air shower is over, the inner door is unlocked, and the voice prompts: "The shower is complete, please exit through the back door".

1.8 After the personnel walk out of the air shower and close the inner door, the system returns to the initial state and waits for the next use.

1.9 After the air shower is completed, the inner door is unlocked. If the personnel inside did not leave the air shower room within the specified time, the system may default that the person may have left and automatically return to the standby state.

1.10 After the lighting is on, if it is not triggered again within the specified time, it will automatically turn off.

 

 