Differential pressure has two core limits. Between clean areas and non-clean areas, the pressure difference should be not less than 10 Pa. Between areas of different cleanliness grades should be not less than 5 Pa. EU GMP cleanroom imposes stricter requirements between grades, typically requiring ≥10 Pa. Dust-generating rooms should be maintained at negative pressure relative to adjacent rooms. Differential pressure is essentially the result of supply, return, and exhaust air balance and is not a fixed value. Common causes of non-compliance during acceptance include clogged return air filters, aged door seals, failure of local exhaust and fresh air damper interlocks, and insufficient fresh air makeup. In engineering practice, the supply air volume is selected at the lower design limit, and the return air damper is provided with a 5%–10% adjustment margin.
The values are 15–25/h for Grade 100,000 areas and 25–30/h for Grade 10,000 areas. Grade 100 areas are not controlled by air changes but by face velocity. Calculations must use the actual room volume. Supply air volume must not only meet dilution requirements but also handle temperature and humidity control and the minimum fresh air volume. Higher air change rates not only reduce steady-state particle concentrations but also substantially shorten the recovery time after production shutdown.
Unidirectional flow cleanrooms rely on face velocity to achieve bulk particle displacement. Typical as-built face velocities are 0.25 m/s for vertical unidirectional flow and 0.35 m/s for horizontal unidirectional flow, with velocity non-uniformity ≤15%. If the velocity is too low, thermal plumes and indoor disturbances may disrupt laminar flow; if it is too high, energy consumption and noise increase, and surrounding contaminants may even be entrained.
The three parameters have clear quantitative relationships: air volume equals air changes multiplied by room volume; unidirectional flow air volume equals face velocity multiplied by the supply air cross-sectional area; and differential pressure is the state resulting from airflow balance.
Before formal acceptance, three self-checks can be performed: close all room doors, allow the system to run stably for 24 hours, then measure and adjust differential pressure; verify the fresh air damper position to ensure the minimum fresh air requirement is met; and, in unidirectional flow rooms, measure face velocity and its uniformity at points below the supply air surface. Only when differential pressure, air volume, and face velocity are stable and controlled can particle and microbial indicators be reliably maintained.