loading

Focuses On Professional Cleanroom Project And Pharmaceutical Cleanroom Equipment.

×
Surgical operating room construction company

Surgical operating room construction company

Our new project operating room smoothly finished installation. The operating room is one of the most strict requirements for aseptic cleanliness in the hospital. The construction, layout, workflow and management of the operating room are all designed around the requirements for sterility. In this project, there are three surgical operating room. The purification and decoration design of the operating room should ensure that the indoor clear height is between 2.8-3m; the width of the corridor is

Our new project operating room smoothly finished installation. The operating room is one of the most strict requirements for aseptic cleanliness in the hospital. The construction, layout, workflow and management of the operating room are all designed around the requirements for sterility.

In this project, there are three surgical operating room. The purification and decoration design of the operating room should ensure that the indoor clear height is between 2.8-3m; the width of the corridor is not less than 2.5m, which is convenient for the movement of people, logistics, and traffic.

The walls and ceilings made of soundproof, strong, fireproof, moisture-proof, and easy-to-clean sandwich panels. The door of the operating room should be wide, without thresholds, to facilitate the entry and exit of flat cars; avoid the use of spring-loaded doors to prevent airflow from entering particles. It is recommended to use sliding doors or clean room purification doors.

The indoor corners are all designed with curved structures, and no 90° corners can be found, so that bacteria have nowhere to hide and avoid corners that cannot be cleared. At the use of connection frame, aluminum alloy profiles play an important role in clean room, such as U shape, inner arc, outer arc and plastic strip.

 

In order to prevent the accumulation of bacteria and dust and maintain a clean working environment, attention should be paid to the selection and installation of lighting lamps in operating rooms: the external shape of the lamps should be simple, not easy to accumulate dust, and easy to wipe. Generally, ordinary grille lamps are not used, but airtight isolation covers are used. The light fixtures not only play a dust-proof effect, but also suppress glare. LED panel light is a good option in operating room.

 

The lamps in the operating room should not be suspended, and should be mounted on the ceiling. At this time, the joint between the lamp and the ceiling should be reliably sealed to prevent dust particles or bacteria from penetrating along the gap.

 

General lighting fixtures in the operating room are evenly arranged on the ceiling around the surgical shadowless lamps. Attention should be paid to close cooperation with construction and equipment professionals, avoiding air outlets and other facilities


If you have more questions, write to us
Just leave your email or phone number in the contact form so we can send you a free quote for our wide range of designs!
Contact Us
Telephone: +86-18241958031/
+86-18913598640
Fax: 86-512-65488640
Whatsapp/Wechat: 008618241958031

Notice:
We hereby declare that our company's only legal contact is through the the above email, Any other similar suffix is a scammer email. 
Address: NO.188 xiangwei road, near junction of xiangwei road and chengyang road (the second floor of south building inside of haiji feiyue) Xiangcheng district, Suzhou city, Jiangsu province, China
no data
Copyright © 2025 Suzhou Pharma Machinery Co., Ltd. | Privacy Policy  Sitemap
Contact us
email
whatsapp
contact customer service
Contact us
email
whatsapp
cancel
Customer service
detect