Laminar flow delivery window is an auxiliary equipment for clean room used to pass small items between clean room and non-clean areas or clean rooms of different grades or different pressures. On one hand, it plays as an airlock to avoid high pressure in high-grade clean rooms from releasing; On the other hand, it can achieve self-purification in the pass process to ensure that the items entering the clean area are clean and reduce cross contamination; the blowing time can be adjusted manually to maximize the self-purification and save energy.
Basic Performance Requirements:
Cleanliness requirement in laminar flow delivery window: class B;
Double shell, arc treatment for inner periphery, seamless connection ensured;
Laminar flow designed with an upward air-sending & downward air-returning mode. The bottom is made of 304# stainless steel and punched, and integrates stiffeners;
Filter: G4 primary filter, H14 HEPA filter;
Wind speed: after HEPA filtration, wind speed at 0.38-0.57m/s (tested at 150mm below the uniform flow membrane);
Differential pressure function: pressure difference of the filter displayed (range: HEPA 0-500Pa/medium efficiency 0-250Pa), accuracy: ±5Pa;
Control function: fan on/off switch, with built-in electronic door interlock; UV lamp with an exclusive switch;
HEPA filter can be removed and mounted via top cabinet for easy maintenance and replacement;
Diffuse plate: made of 304# stainless steel screen
Dimensions (mm) | W800×H1200×D670 | W1000×H1400×D870 |
Workspace dimensions (mm) | W600×H600×D600 | W800×H800×D800 |
Nozzle air speed (m/s) | 0.3~0.9 | |
Air shower time (s) | Manual control | |
Cabinet material | Cabinet and internal wall made of SUS304# stainless steel | |
HEPA filter size | 487×487×93 | 610×610×93 |
Filtration efficiency | (H14) 99.995%@0.3μm | |
Fan power (W) | 165W | |
Power supply | 220V/50Hz |