Determination of temperature and humidity and airflow pattern in clean room

Determination of temperature and humidity and airflow pattern in clean room

Before the measurement of indoor air temperature and relative humidity in the clean room, the purification air-conditioning system has been running continuously for at least 24 hours. For places with constant temperature requirements, according to the requirements for the fluctuation range of temperature and relative humidity, the measurement should be carried out continuously for more than 8 hours. The measurement interval is small...

Text label: clean room engineering, clean room measurement, temperature and humidity measurement

Determination of temperature and humidity and airflow pattern in clean room

Before the measurement of indoor air temperature and relative humidity in the clean room, the purification air-conditioning system has been running continuously for at least 24 hours. For places with constant temperature requirements, according to the requirements for the fluctuation range of temperature and relative humidity, the measurement should be carried out continuously for more than 8 hours. The measurement interval is not more than 30min; according to the fluctuation range of temperature and relative humidity, the corresponding instrument with sufficient accuracy should be selected for measurement; indoor measurement points are generally arranged at the air supply and return air outlets, and representative locations in the constant temperature working area. Center and sensitive components; all measuring points should be at the same height, 0.8m from the floor, or arranged on several planes with different heights from the ground according to the size of the constant temperature zone. The distance between the measuring points and the outer wall surface should be greater than 0.5m.

Indoor airflow pattern detection, the purpose is to check whether the airflow pattern in the clean room meets the cleanliness. If the airflow pattern in the clean room cannot meet the requirements of airflow arrangement, the cleanliness in the clean room will not be or difficult. To meet the requirements; for a one-way flow clean clean room modular, one longitudinal and one transverse section is generally selected, and one measuring point is arranged on the horizontal plane with a height of 0.8m and 1.5m from the floor, and the distance between the measuring points is 0.2m-1.0m. It can also focus on the layout; for a horizontal one-way flow clean room, choose one section and one working area height level, and three cross-sections 0.5m away from the supply and return air walls and the center of the room; for non-one-way flow clean rooms For the room, you can choose to arrange the measuring points through the vertical and horizontal sections of the center of the representative air outlet and the horizontal plane of the working area height. 1.0m, and the measuring point should be arranged on the center line between the two tuyere. Zhongjing Global Purification can provide consulting, planning, design, construction, installation, transformation and other supporting services for clean rooms and clean workshops.

The detection of indoor planktonic bacteria and settled bacteria is an important means to ensure the air quality of the air-conditioning system. There are two detection methods: air suspension microorganisms and sedimentation microorganisms. The sampled substrates are cultured in a constant temperature box at 37°C and 48H. Counting after the production of bacteria, the sampling vessel and culture solution used must be disinfected and sterilized, and the sampling points can be arranged evenly or in a representative area; the suspended microorganism method should use centrifugal, slit and pinhole collisions. The sampling time should be determined according to the concentration of microorganisms in the air, and the number of sampling points can be the same as the number of measuring points for measuring air cleanliness; for the sedimentation microorganism method, a petri dish with a diameter of 90mm should be used, and the sampling should be carried out after settling on the sampling point for 30 minutes; During bacterial determination, the petri dish should be arranged in a representative location and a location with minimal airflow disturbance. The preparation of the sampling device before sampling and the treatment after sampling should be carried out in a negative pressure laboratory equipped with high-efficiency air filter exhaust. The temperature of the laboratory should be 22±2℃ and the relative humidity should be 50%±10 %; the sampling instrument should be sterilized, and the exhaust gas of the sampling device should not pollute the clean room; the number of sedimentation vessels, sampling points, culture medium, culture temperature, and culture time should be implemented in accordance with the relevant specifications; the sampling of planktonic bacteria samplers If the straightness is greater than 100L/min, the air velocity of the collision medium should be less than 20m/s.

SUZHOU PHARMA MACHINERY CO.,LTD. specializes in undertaking corporate offers to cater the needs of different companies.

SUZHOU PHARMA MACHINERY CO.,LTD. looks forward for the meeting and the association with your esteemed company.

SUZHOU PHARMA MACHINERY CO.,LTD.'s CUSTOM SOLUTION SERVICES are sturdy, easy to operate, friendly work machines that deliver high-quality extraction machine for extraction machine purposes.

The rising extraction machine consciousness observed worldwide are expected to be key factors driving the demand for extraction machine CUSTOM SOLUTION SERVICES.

The risk of extraction machine is reduced by extraction machine with the consumption of .

GET IN TOUCH WITH Us
recommended articles
Project
Clean Room Pressure Difference Influencing Factors And control Methods
A professional clean room must control the pressure difference to ensure that air flows from clean areas to non clean areas and from high cleanliness areas to low cleanliness areas during normal use, thereby maintaining clean air in the clean room at all times.
In depth Analysis of Sterile Isolators
Aseptic isolators are enclosed spaces composed of rigid and/or flexible barrier materials. They contain an integrated vaporized hydrogen peroxide (VHP) sterilization system, which can repeatedly sterilize the air inside the isolator and effectively exposed surfaces to remove the bioburden.
Clean Room PVC Floor
Cleanroom pvc flooring is a polyvinyl chloride (PVC) material specifically designed for clean room environments. It has a high density and smooth surface.
Thoughts on the Applicability of Laminar Flow Interference Testing in Clean Areas

In clean area management and quality control, laminar flow interference testing has received much attention, and whether it is only applicable to Class A laminar flow remains to be considered.
no data
Contact Us
Telephone: +86-18241958031/
+86-18913598640
Fax: 86-512-65488640
Whatsapp/Wechat: 008618241958031

Notice:
We hereby declare that our company's only legal contact is through the the above email, Any other similar suffix is a scammer email. 
Address: NO.188 xiangwei road, near junction of xiangwei road and chengyang road (the second floor of south building inside of haiji feiyue) Xiangcheng district, Suzhou city, Jiangsu province, China
no data
Copyright © 2025 Suzhou Pharma Machinery Co., Ltd. | Privacy Policy  Sitemap
Contact us
email
whatsapp
contact customer service
Contact us
email
whatsapp
cancel
Customer service
detect